Global Sources
EE Times-India
Stay in touch with EE Times India
 
EE Times-India > Power/Alternative Energy
 
 
Power/Alternative Energy  

Liquid-cooled AC/DC maximises thermal efficiency

Posted: 14 Dec 2006     Print Version  Bookmark and Share

Keywords:thermal management  heat management  rectifiers  AC/DC  Transistor Devices 

The LCPM series of 7kW AC/DC front-end rectifiers from Transistor Devices is liquid-cooled for maximum thermal efficiency in data and computer centres.

Up to six modules, each 12-by-2.8-by-18 inches (HWD) can fit side by side on a 17.5-inch shelf to deliver up to 42kW of regulated power from the 3-phase universal power mains (195-265Vac, 47-63 cycles). Efficiency is greater than 90 per cent and the power factor is better than 0.99.

The modules are typically cooled with water or a water ethyl glycol mixture, which enters and leaves the module via a blind mated pluggable liquid coupling. The unit is available with either aluminium or copper piping to assure no incompatibility of metals.

Contact the company directly for pricing information.

- Vince Biancomano
eeProductCenter




Comment on "Liquid-cooled AC/DC maximises therma..."
Comments:  